    System – Trouble Display Options

    LOCATION 0 is Defaulting the Panel, Master User code or Missing devices…

    This location allows you to default to the panel, user codes and their properties, and bus-wired peripherals. Refer to Table 4 for the values that can be programmed, and their actions. 

    [#] [1479] [*] = Installer Menu 

    [0] [*]  = Default Panel - Action 

    [VALUE] = select specific data code as the table below to default

    [*] = to confirm and updating the settings.

    [#] [Installer code] [*] [0] [*] [Value] [*]

    Table 4: Defaulting Data

    Value

    Action

    0

    Will reset all locations and ID’s to the factory default values. (Master User Code 1234) 

    1

    Will default the Primary Master User Code back to 1234 - or 123456 if 6 digits are being used. 

    Master User Code properties will also be defaulted. 

    2

    Defaults ALL user codes and their properties. 

    3

    Defaults ALL keypads. 

    4

    Remove Missing Devices. 

    Any missing devices (keypads, for example), will have its address freed up, making its address available for a new device when it is enrolled. This MUST be performed when replacing a faulty device. (You must wait for 30 seconds from device failure or removal.) 

    5

    Default “Central Monitoring Mode”. Defaults DTMF numbers, dialling options, reporting options, reporting code options and sets some options not to factory settings. (Implemented in vers.2) 

    6

    Default “Private Reporting mode”. (Sets some options not to factory settings) 

    (Implemented in v2) 

    7

    Defaults all wireless zones and settings 